Building Size:
226,030 SF
Lot Size:
42.20 Acres
Property Description
Year Built
1968 / 1992
The original facility was built in 1968. 20,327 square feet was added in 1992.
Quality
Very Good
Office
9,044 SF
Additionally, there is 4,849 sf of support area.
Dimensions
483 x 360
Ceiling Height
Min: 15' 3", Max: 22'
Ceiling Comments
Original Plant: 15’3” clear at the eave.
1992 Addition: 20’ clear at the eave to 22’ clear at the center.
Column Spacing
40' x 30'
Column Comments
8" steel H
Column Type
Steel H
Roof
Rubber membrane installed in 1981 through 2004.
Floors
5" Concrete - 5" to 6” concrete floor
Walls
8” pre-cast insulated panels.
Lighting
75% of the plant is 250 watt metal halide. 25% of the plant is 250 watt sodium vapor.
Loading
South: 2-7’x9’ manual overhead doors w/manual levelers, lights, bumper pads & seals
1–8’x10’ manual overhead DI door
West: 4–8’x9’ manual overhead doors w/manual levelers, lights, bumper pads & seals
1–12’x12’ manual overhead door w/manual levelers, lights, bumper pads & seals
East: 1–12’x12’ rapid rollup DI door
North: 1–12’x14’ manual overhead DI door
1–14’x14’ manual rollup DI door
1–8’x10’ manual overhead DI door
1–12’x10’ manual rollup DI door
Parking
388 paved, marked and lighted spaces
Rail
No
Gas
PSNC, 4" line
Water
City
Sewer
City
Power
Duke Energy Company
Primary: 44 kv/575v 3 wire delta delivery
Transformers: 3 single phase transformers with total capacity of 11,300 kva
Secondary: 4 – 2,000 amps GE switchgear at 575 volts, 3 phase
1 – 1,600 amps Siemans switchgear at 575 volts, 3 phase
Distribution: Bus duct; 200 amp and 400 amp bus bars.
Heat
Gas
Gas fired unit heaters
Air Conditioning
Yes - There is air conditioning in the manufacturing and the office.
3 - 450 ton Trane Chillers with R-11 refrigerant installed in 1968.
1 - Twin Cooling Tower
1 - Single Cooling Tower
Sprinklers
Yes - 100% wet system with an 8” fire loop on seven external hydrants.
Risers: 7
Static Pressure: 120 P.S.I.
Flow Rate: 1000 gpm
1 – Electric Pearless pump that produces 1000 gpm
1 – Electric Jockey Pump that maintains pressure at 120 P.S.I.
1 – Ground Level water storage tank for fire protection that is 200,000 gallons
Air Line
Air lines distributed throughout.
1 Sulair water cooled facility at 1250 cfm
1 Quincy water cooled facility at 1250 cfm
1 Ingersol Rand air dryer at 1250 cfm
2 – accumulation tanks
Equipment
Industrial Air Inc. – Clima Cell air handling unit installed in 1992. Unit is used for process heat and cooling for die castings.
Special Features
1 – 6,000 gallon above ground non-hazardous waste tank.
* 3 – Outbuildings
1 – 1,800 sf equipment shed
1 – 2,000 sf dyked chemical storage building with explosion proof lighting
1 – 640 sf dyked chemical storage building.
* No pre-treatment facilities
Last Use
Manufacturing staters for commercial air conditioning compressors
Hart Corporation - Thomas Turner, SIOR
-
7422 Carmel Executive Park, Suite 216 - Charlotte, NC 28226
-
704.541.1393
-
tturner@hartcorp.com
All information furnished is from sources deemed reliable, but no warranty or representation is made as to the accuracy thereof and same is submitted subject to errors, omissions, change of price, rental or other conditions, prior sale, lease or financing, or withdrawal without notice. No liability of any kind is to be imposed on the broker herein.